Wiki
Home » Blog » Wiki » Resistance Grounding System

Resistance Grounding System

Low Resistance Grounding:
1. Limits phase-to-ground currents to 200-400A.
2. Reduces arcing current and, to some extent, limits arc-flash hazards
associated with phase-to-ground arcing current conditions only.
3. May limit the mechanical damage and thermal damage to shorted
transformer and rotating machinery windings.
4. Does not prevent operation of overcurrent devices.
5. Does not require a ground fault detection system.
6. May be utilized on medium or high voltage systems. GE offers low
resistance grounding systems up to 72kV line-to-line.
7. Conductor insulation and surge arrestors must be rated based on the lineto-
line voltage. Phase-to-neutral loads must be served through an
isolation transformer.

High Resistance Grounding:
1. Limits phase-to-ground currents to 5-10A.
2. Reduces arcing current and essentially eliminates arc-flash hazards
associated with phase-to-ground arcing current conditions only.
3. Will eliminate the mechanical damage and may limit thermal damage to
shorted transformer and rotating machinery windings.
4. Prevents operation of overcurrent devices until the fault can be located
(when only one phase faults to ground).
5. Requires a ground fault detection system to notify the facility engineer that
a ground fault condition has occurred.
6. May be utilized on low voltage systems or medium voltage systems up to
5kV. IEEE Standard 141-1993 states that “high resistance grounding
should be restricted to 5kV class or lower systems with charging currents
of about 5.5A or less and should not be attempted on 15kV systems, unless
proper grounding relaying is employed”.
7. Conductor insulation and surge arrestors must be rated based on the lineto-
line voltage. Phase-to-neutral loads must be served through an
isolation transformer.

Conclusion:
Resistance Grounding Systems have many advantages over solidly grounded systems including arc-flash hazard reduction, limiting mechanical and thermal damage associated with faults, and controlling transient overvoltages. High resistance grounding systems may also be employed to maintain service continuity and assist with locating the source of a fault.
When designing a system with resistors, the design/consulting engineer must consider the specific requirements for conductor insulation ratings, surge arrestor ratings, breaker single-pole duty ratings, and method of serving phase-to-neutral loads.

Post a Comment:

    
Calculate (8 - 7) =

You may also like:

A low impedance fault is usually a bolted fault, which is a short circuit. It allows a high amount of fault current to flow, and an upstream breaker or fuse usually senses the high current and operates, ending ...
My cable size and transformer size should give me maximum 3% on the worst 6% to 10%. If it is the single only equipment on the system then maybe you can tolerate 15%. If not, dip factor may affect sensitive ...
The trend toward lower losses in power converters is not apparent in all of the applications of power converters. It is also not apparent that the power converter solution and its losses for a given market ...
If you're planning to use a Soft Starter or VFD for motor starting, you need to specify the horsepower rating, voltage rating, rated frequency, the type of motor (induction wound rotor or induction squirrel ...
Soft Start and Soft Stop is especially useful with pumping fluids where torque transients often cause water hammer effects, and in some instances, failure to gradually slow the fluid down before stopping, can ...
Gozuk Service Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.

Featured

Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ... energy consumedA frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ... Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ... Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ... Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...

In Discussion