VFD control loop circuit faults analysis

The affection on variable frequency drive life in the control loop circuit is the power part, the buffer capacitor in smoothing capacitor and IPM board. The ripple current pass the capacitor is a fixed value which won't be affected by the main circuit, so its life is mainly determined by the temperature and power-on time. Since the capacitors are soldered to the circuit board, it difficult to determine the capacitor deterioration by measuring the electrostatic capacity. Generally, we calculate its life base on the ambient temperature and service time.

Power supply circuit provides power to the control circuit board, IPM drive circuit, operation display panel and cooling fan, the power is obtained from the main circuit DC voltage rectified by the switching power supply. Therefore, if one power short circuit, besides itself damaged, also affect other parts power supply, such as misoperation causes power source and the public ground short circuit, result in switching power supply circuit board damaged, the fans power supply short circuit etc. Generally it's easy to find out by observing the power supply circuit board.

Logic control circuit board is the core of a variable frequency drive, it includes CPU, MPU, RAM, EEPROM etc large scale integrated circuits, the failure rate is very rare due to high reliability. But sometimes all control terminals closed simultaneously during startup which will cause the VFD drive appear EEPROM fault, in such case, just reset the EEPROM.

IPM circuit board contains drivers and buffer circuit, and over-voltage, phase loss protection circuits. Logic control panel PWM signal input to IPM module by voltage drive signal optical coupling, so, we should measure the IPM module optical coupling during module detection.

Post a Comment:

    
Calculate (8 + 8) =

You may also like:

You know standards for the electronic industry have been around for decades, so each of the interfaces we have discussed does have a standard. Those standards may be revised but will still be used by all ...
This could be internal corona discharge. The switchgear should be de-energized and closely examined. That means pump out the SF6 and take it apart. Examine all insulating components. Especially if the sound ...
Manufacturers are able to achieve exceptional density by virtue of High frequency resonant topologies, but they have to achieve high efficiencies too; Else, they will generate so much heat that they cannot ...
We are frequently changing tap position of Unit station transformer due to voltage problem. What are the impacts on transformer life and is there any solution to minimize this?
The noise level created by the motor at any speed is in a fixed environment, take two motors same HP, Speed, Enclosure, and the applied voltage could be a factor of the noise, the installed conditions of a ...
Gozuk Service Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.

Featured

Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ... energy consumedA frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ... Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ... Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ... Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...

In Discussion