Motor controls
Home » Blog » Motor controls » SCR broken failure in soft starter

SCR broken failure in soft starter

SCR's are limited to a maximum current rating, as well as a maximum voltage rating. In addition, the number of starts per hour is also limited. A combination of voltage spikes, too many starts per hour, or too much current during a start will destroy a soft starter. Phase imbalance for either voltage or current will cause an SCR to fail, as will a single phase condition on a 3-phase motor. What also needs to be considered is the load being started. If it is a high starting torque load it may require a heavy duty version of soft starter to get it going.

SCRs rarely "break" but they do short out, or rather, become full time conductors. The only thing that can cause this is excess tightening torque or clamping pressure. If on the other hand that the soft starter is giving an indication that one SCR is shorted, then that is where the comments from Terence Smith come to play. It will be either a voltage spike, a current spike, or excess heat caused by excessive starting current or starts per hour.

But reactors will not really help and will increase the throughput losses in the soft starter, I would not waste time on that. Starting a spinning motor is not an issue with soft starters either. Both of these are potential issues with VFD, totally different animal.

If the SCR fault covers the unbalanced starting current too, there is another possibility. At the motor connection box, on the side of the motor there are 6 bolts with screws, for connecting cable, star-delta cooper sheets, and motor coils. The lowest places on the bolt are the clamps of the motor coils, which is followed by a bolt. Over this bolt there are the star-delta sheet, bolt, cable connection clamp and upper the 3-rd bolt. In many cases the lowest screw, at the coil clamp is not tight enough. The maintenance electricians never check them, because it doesn't belong to the cable installation. In many cases they occurred output phase fault in inverters and phase faults in soft starters.

Post a Comment:

    
Calculate (7 - 5) =

You may also like:

When conducting insulation testing, the most important consideration is consistency. Always test at the same location, use the same test voltage, perform the test for the same amount of time, and use the same ...
A lighting control panel will have mostly single-pole breakers with phase-to-neutral branch circuits feeding lighting circuitry. There is the added possibility of having either 'smart' breakers or integral ...
Using solar output distributed to offset the dirtiest, most expensive and most distribution grid loading power enhances and optimizes the value and worth of that solar generated power - both economically and ...
Unfortunately my report was based on experience for old engineer and recommendation of Manufacturer. One of the most important thing about brushes in high current density environments is uniformity. If there ...
Koil can make the synthesis (i.e. design the winding layout from slot-pole combination) only for symmetrical windings. To have a symmetrical 3-phase winding the back EMFs must be equal and out of phase of 120 ...
Gozuk Service Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.

Featured

Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ... energy consumedA frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ... Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ... Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ... Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...

In Discussion