Home » Blog » Wiki » Difference between DCS and RTU

Difference between DCS and RTU

DCS distributed control system: you can control the system within a certain given facility from different locations, either control room or other places, and you should keep in mind this facility could be a in several locations but yet, hard-wired interconnected. while
RTU (remote Terminal Unit): you can control the system remotely through internet or a secure satellite connection which in not recommended for sensitive operations/process but it is ok for stand alone and not crucial systems. and more.

DCS as part of SAS (Substation Automation System) is based on local control of relays, meters and switchgear and automation as per required logic and programs that could be hardwired for serial protocols (like DNP 3.0) or through fiber optic when UCA 2.0 or IEC 61850 protocols are used.
For RTU, it's just interface between substations' I/O signals and dispatching center (SCADA) through communication links and specific protocols (such as IEC 101,104, Indactic, DNP 3.0, etc.). In other words, RTU has no controlling role by itself, but DCS as part of SAS has all programmed control logic within substations and without even connecting to dispatching center.

For Electrical Network Distribution, a System is required for controlling, Load dispatch as well as monitoring. Therefore Distribution Management System (DMS) or DCS to be adopted as an integrated System. They are simply like SCADA. Composed from Hardware, software, interfacing means & communication media / protocol as indicated above.
RTU (remote Terminal Unit) include Processor and all the required interfacing facilities as well as I/O(s) Modules.

The brief description of such system may be as follows:
The Substation prescribed Signals (MV switchgears, Transformer, Substation Auxiliary Equipment, etc.) to be hardwired to a marshaling box to Interface Cubicle where RTU located, RTU to be patched to the interface plate. Via the selected media “say FOC” the signals will be transferred to the DMC/DCS Control Centre. Accordingly, the real time status of the NW can be monitored and controlling can be achieved from remote.

The aforesaid Signals to be listed and sorted as per the required application to facilitate system configuration, integration and programming (unique address, function, type, is it required for control, monitor or both, which is digital & which is analogue, etc.).

Post a Comment:

    
Calculate (6 - 7) =

You may also like:

In motor protection panel when 3 fuses are provided for short circuit protection, Is it always a condition that during short circuit minimum 2 fuses should be blown? If yes or no then why? Its essential ...
A few years back, I had a devil of time getting some OPC Modbus TCP drivers to work with Modbus RTU to TCP converts. The OPC drivers could not handle the 5 digit RTU addressing. You need to make sure your OPC ...
DC drives with motor field control provide coordinated automatic armature & field voltage control for extended speed range & constant-horsepower applications. The motor is armature-voltage-controlled ...
The baseline figure should be obtained from either factory or during initial commissioning (as per factory condition). So performing commissioning in the rain, dirty surface, high humidity may result in low ...
Synchronous motors generally offer more efficiency than induction ones, and hence in higher ratings (about 5000 hp and higher) they may be more cost effective considering Life Cycle Costs. The exact size of ...
Gozuk Service Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.

Featured

Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ... energy consumedA frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ... Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ... Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ... Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...

In Discussion